Trench Heating typically involves a convector recessed into a steel casing within a computer or screeded floor, with a roll-up floor grille. HCP's products are ideal for combating cold down draughts and condensation, characteristics often associated with full and half height glazing and provide an effective heat source where wall space is limited.

To find about more about HCP’s range of Trench Heating products, you can click here to download our Trench & Perimeter Heating brochure (2,683k PDF format)

Drawings

HCP’s trench heating units offer Low Pressure Hot Water (LPHW) or electric elements. The units can be fully or partly recessed, or floor-mounted depending on the project's requirements

Fully recessed
Semi recessed
Floor mounted

 

Specifications

HCP’s elements are manufactured from copper tubing, which are available in diameters of 15, 22 or 28mm; enhancing the heating output is a profiled grille of extruded aluminium. Our standard systems are available in nine sizes, but by increasing or decreasing the diameter of the copper tubing and aluminium grille and/or the length of the element, a wide range of heating outputs can be achieved.

Listed below is the performance data for HCP’s nine standard systems.

Model *Output
watts/metre
Tube Diameter
mm
LTU/J 250 15 or 22
LTU/JJ/S 380 15 or 22
LTU/N 485 15, 22 or 28
LTU/W 645 22 or 28
LTU/JJ 645 15 or 22
LTU/FF 645 15 or 22
LTU/FN 805 15 or 22
LTU/NN 970 15, 22 or 28
LTU/WW 1290 22 or 28
CORRECTION FACTORS
Variations in
water velocity
lVariations in T
Water
Velocity in
metres/sec
Correction
Factor

T
m.w.t. - e.a.t.
K
Correction Factor
0.08 0.90 30 0.38
0.10 0.91 35 0.47
0.15 0.92 40 0.57
0.25 0.93 45 0.67
0.28 0.94 50 0.77
0.30 0.95 55 0.88
0.35 0.96 56 0.90
0.50 0.97 57 0.93
0.75 0.99 58
0.95
1.00 1.00 59 0.98
1.35 1.02 60 1.00
2.00 1.03 65 1.12
    70 1.24
    75 1.34
    80 1.47

Dimensions

Pictured below are line drawings of the nine standard systems available from HCP.

LTU/J
LTU/JJ/S
LTU/N
LTU/W
LTU/JJ
LTU/FF
LTU/FN
LTU/NN
LTU/WW

Design

Design and adaptability are fundamental to the HCP philosophy of customer commitment, so whatever your space restriction or output requirement we can design a system to suit your needs. Should an installation require a special unit to be made, HCP can design and manufacture a prototype unit in advance of the contract in order that the specifier, contractor and client can test the system and ensure maximum satisfaction.

Options

From casings with front panels, cable trays, partition cover plates or acoustic baffles HCP offer a number of options to tailor our product to your requirements. Grilles can be oversized or made to run in linear lines and casings can be propped up by cantilevered supports. See diagrams below.

Front Panel
Partition cover plates and casing baffles
Cable Trays
Linear Aluminium Grilles
Cantilevered Casing Support
Over Sized Grilles
 